Supply via Isolator
230V 50Hz 1 Pha
Burners
Zone A
Drawing No. : 900289 R8
Supply to inline
burners
(HEAT 1 OUTPUT)
(LIVE)
(NEUTRAL)
NOTES:
REMOTE SWITCH INPUTS
should be connected by 6A mains
Max length is 100m.
Low voltage switching inputs to be
normally open (closed circuit to
enable).
Connect to B0 & B1 for remote ON
(ie BMS time control).
Connect to B0 & B2 for remote
OFF (ie door interlock. remote
frost etc).
*The power supply is non-isolated,
therefore all wiring to the control must be
mains rated.
REMOTE SENSOR(s) may be
placed at a max distance of 100m
from the control unit, using
screened 6A mains* cable.
Wiring should be kept separate
from mains wiring to minimise
noise pick up. Set within Engineers
functions for remote sensor.
*The power supply is non-isolated,
therefore all wiring to the control must be
mains rated.
Black Bulb
Sensor
Note: Connection to the
burners MUST be made
via a 3A fused spur.
!
!
FUSE RATING
!
41 40 95 1/L 2/N 106
B1 B0 B2 S/R0S/R1
C
SmartCom
Singlezone
NEUT
LIVE
(COMMON)
(REMOTE ON)
(REMOTE OFF)
eg Door
Remote OFF
(where applicable)
Remote ON
(where applicable)
eg B.M.S.
4-Core Armoured Cable
FAN MOTOR
415V 3-Phase Supply.
Motor must be wired DELTA
3 Phase
Isolator
Mains Voltage
230V AC
(FAN CIRCUIT)
(FAN CIRCUIT)
SUPPLY VIA ISOLATOR
ELECTRICAL INPUT
415V 3P 25A
FAN TYPE
BH300
L2L3 L1 L1
1
U V W
2
34
NN
Volt free
Fan Trip
Indication
by others
Local Relay
Unit
THE LOCAL RELAY UNIT houses a 3pha
motor contactor and overload plus any
additional fan logic circuitry.
Exhaust
Fan
Figure 4.m. NRV Schematic interconnecting wiring. BH300 three phase fans controlled by
SmartCom3 via three phase Local Relay panel. (single zone shown)